Sobretensiones por resonancia serie en el sistema de potencia de plantas petroquímicas

J. García, O. A. Reyes, D. Olguin

Producción científica: Contribución a una revistaArtículorevisión exhaustiva

Resumen

The purpose of this study was to determine the conditions under which resonance overvoltages occur in the petrochemical plant power system in Mexico. This analysis was carried out by means of simulations of the electrical system using ATPDraw under fault conditions. The simulation results showed that the resonance appeared from 2 to 18.5 kHz, with a maximum magnitude of 20.5 p.u. It was found that this phenomenon depended on the grounding scheme of the plant. Modification of the interconnection scheme of the power system was required in order to avoid these overvoltages. Based on the simulations carried out, it was necessary to electrically isolate the generators usingunit transformers in a delta - star connection.

Título traducido de la contribuciónSeries resonance overvoltages in petrochemical plant power systems
Idioma originalEspañol
Páginas (desde-hasta)73-82
Número de páginas10
PublicaciónInformacion Tecnologica
Volumen16
N.º6
EstadoPublicada - 2005

Palabras clave

  • Electrical power system
  • Neutral grounding
  • Overvoltage
  • Series resonance