Optimum hot water temperature for absorption solar cooling

A. Lecuona, R. Ventas, M. Venegas, A. Zacarías, R. Salgado

Producción científica: Contribución a una revistaArtículorevisión exhaustiva

62 Citas (Scopus)

Resumen

The hot water temperature that maximizes the overall instantaneous efficiency of a solar cooling facility is determined. A modified characteristic equation model is used and applied to single-effect lithium bromide-water absorption chillers. This model is based on the characteristic temperature difference and serves to empirically calculate the performance of real chillers. This paper provides an explicit equation for the optimum temperature of vapor generation, in terms of only the external temperatures of the chiller. The additional data required are the four performance parameters of the chiller and essentially a modified stagnation temperature from the detailed model of the thermal collector operation. This paper presents and discusses the results for small capacity machines for air conditioning of homes and small buildings. The discussion highlights the influence of the relevant parameters.

Idioma originalInglés
Páginas (desde-hasta)1806-1814
Número de páginas9
PublicaciónSolar Energy
Volumen83
N.º10
DOI
EstadoPublicada - oct. 2009

Huella

Profundice en los temas de investigación de 'Optimum hot water temperature for absorption solar cooling'. En conjunto forman una huella única.

Citar esto